Box fill calculator

Count what's in the box — conductors, clamps, devices, grounds — and see whether it fits the box you picked, per NEC 314.16.

Back to AstralLearn

Conductors entering the box

×
Fits
22.5 in³box 30.3 in³ · 74%
Conductors
13.5 in³
Clamps
2.25 in³
Devices
4.5 in³
Supports
0 in³
Grounds
2.25 in³

Volumes count by the largest conductor present (12 AWG) per NEC 314.16(B).

How it works (NEC 314.16(B)): each conductor entering = 1 volume of its size; all clamps together = 1 of the largest; each support fitting = 1; each device yoke = 2; all grounds together = 1 of the largest ground. The total must not exceed the box's marked volume.

Educational reference — verify against the current NEC and your AHJ. Need it inspected and permitted? Call a licensed C-10 → (650) 562-8594.